Contaminant-Free Storage and Mix

 

 

Paint Kitchens

Paint kitchens designed for either indoor or outdoor applications.
• Two-hour fire rated building, 4-hour available
• Spill containment sump
• Explosion-Proof ventilation system
• Portable design

 

Code Compliance

GFS Paint Kitchens comply with National Fire Protection Association Fire Code - NFPA-30, Flammable and Combustible Liduids. International Fire Code.

 

 

Paint Kitchens
Contaminant-Free Storage and Mix

 

 

Standard Features:


Explosion Relief Vent Panels: Explosion-relief vent panels designed to release at a maximum internal pressure of 20 psf. Location - rear wall of building. Each panel is sealed to prevent gases from escaping to the exterior. Explosion-relief panels are equipped with FMRC-approved explosion-relief fasteners. This system complies with Factory Mutual requirements for storage of Class IA and dispensing of Class IA and IB liquids.


Interior Lighting: Explosion proof incandescent ceiling mounted with guard, glass globe and 300 Watt lamp.


Walls: 6" wide steel studs spaced 12" covered with two layers of 5/8" type exterior gypsum wallboard each side. Skinned with ASTM A591, 18-gauge steel white polyurethane coated panels.


Roof/Ceiling: The roof consists of joists 7" deep and spaced
at 12" on center. Two layers of gypsum board are attached to the interior and covered with 18-gauge white polyurethane coated steel panels. Exterior is skinned with 18-gauge white coated steel panels.


Steel Grating: 1" bars painted black.

 

Floor Support: 6" steel beams run the entire length of the housing and are positioned for holding heavy capacities.

 

 

 

Ventilation System: 680 cfm @ 3/8 sp for optimum air exchange rating.

 

Control Panel: NEMA 4 water/oil tight enclosure incorporates voltage per customer requirements, UL listed system, fuse block, and operating switches.

 

Sump Construction: Liquid tight heavy gauge sheet steel supported by exterior welded steel risers to allow for under sump leak inspection.

 

Extra Large Spill Containment: Sump holds 30% of locker's
liquid storage capacity surpassing regulatory and FM requirements.

 

Static Electricity Bonding/Grounding System: Interior wall-mounted grounding lugs and exterior grounding connection, separate 8-ft. grounding rod and cable for customer installation.

 

Design Specifications:
- Snow Load: 60 psf
- Wind Speed: 120 mph, exposure D (36 psf)
- Floor Load: 300 psf
- Internal Pressure: 166 psf
- Seismic Design Category D

Inside Dimensions

Outside Dimensions

Sump Capacity

Length

Depth

Height

Length

Depth

Height

Height
(opt. Sump)

Gallons

10'

8'

8'3"

11'6"

9'8"

10'0"

10'6"

375

16'

8'

8'3"

17'6"

9'8"

10'0"

10'6"

600

22'

8'

8'3"

23'6"

9'8"

10'0"

10'6"

825

28'

8'

8'3"

29'6"

9'8"

10'0"

10'6"

1,050

 

Paint Kitchens
Contaminant-Free Storage and Mix

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Configurations:

 

Air Conditioning Units: Externally mounted on roof or at grade. Designed for specific applications.

 

Building Code Compliance: Complies with additional regulations set by: IBC, and IFC.
- Additional 6" of sump height to contain 20 minutes of sprinkler water plus single largest container.
- Adaptions to accept ducting at explosion relief panels. This
allows for easy vent ducting to outside. Additional duct panels
not included.

- Special State compliance, contact GFS.

 

Outside Locations: Security bars on explosion relief, single ply roof membrane, insulated walls and ceiling.

 

Bulkhead Fittings: Factory installed for paint and airline needs. Can be mounted in the walls or ceiling.

 

Explosion Relief Panels: Roof explosion-relief vent panels available for indoor applications ONLY.

 

CUSTOM SIZES AND CUSTOM DOORS AVAILABLE:
Custom sizes may require some field assembly.

Fire Protection Options:
- Dry Chemical Systems: A pre-engineered industrial Dry Chemical fire extinguisher system that incorporates a network of piping and discharge nozzles as defined by NFPA-17. A "Total Flooding" system is used whereby the Dry Chemical is discharged into the building enclosure. This system includes an agent storage tank, actuator, quick release, flow nozzles, 212° F fusible link, pull-station, and alarm. UL listed. The Dry Chemical System cylinder may need to be charged by customer upon arrival.
- Water Sprinkler-Systems: Featuring sprinkler heads and exterior hook-ups connecting adapter in accordance with NFPA-13. May require additional sump capacity.


Fiberglass Floor Grating: 1" thick, fire retardant, corrosion and UV resistant, permanently bonded quartz grit for anti-skid surface.

 

Liquid Level Detection System with Alarm: Features a fiberoptic sensor and float.

 

Ramp: Access ramp fabricated from heavy-duty plate steel. One-piece fabrication without welding points providing non-corrosive, long life finish. 6:1 ratio run to rise 12" h x 70-1/2" l x 33" w. Painted white polyurethane with 2" wide grip tape at 4" intervals.

 

Heaters, Convection: Designed for hazardous locations, Class 1, Division 1, Groups C and D environments. Custom sizes for each specific application.

 

 